Modbus RTU poll and scan time
Enter your line settings and read load to roughly see the time of a single read and the time the master needs to scan all devices once. The result is a lower-bound estimate; real time is longer depending on devices and master software.
Formulas and assumptions
- Character: 1 start + 8 data + parity (0 or 1) + stop bits. 11 bits for 8E1 and 8N2, 10 bits for 8N1.
- A read request is 8 bytes. The response is
5 + data bytes(address, function, byte count, 2-byte CRC). Data bytes:2 × quantityfor FC03/04,⌈quantity / 8⌉for FC01/02. - Single read:
(request + response bytes) × bits / baud + device delay + n × t3.5 - t3.5: at 19200 baud and below,
3.5 × character time; above that a fixed 1.75 ms (Modbus serial line guide recommendation, secondary source; confirm with the official document). Some devices require a longer silence. - Cycle:
devices × reads per device × single read time. - Not included: timeouts and retries, master software processing time, broadcast and write commands, USB/gateway converter latency.
- Limits: FC03/04 up to 125 registers, FC01/02 up to 2000 bits, 1–247 devices.