4-20 mA ↔ PLC raw value scaling
Enter a current (mA) or a PLC raw value to see the equivalent, the engineering value and the NAMUR NE43 status. You enter the raw range: these values are in your PLC and analog module documentation; the tool does not guess them.
Formulas and assumptions
- Linear mapping:
raw = rawMin + (mA − 4) / 16 × (rawMax − rawMin) - Process value:
value = procMin + (raw − rawMin) / (rawMax − rawMin) × (procMax − procMin) - Currents outside 4–20 mA are extrapolated linearly, not clamped. A real module may saturate or clamp the raw value there; check the module documentation.
- The raw range may be reversed (max < min).
- NE43 thresholds: ≤3.6 mA and ≥21 mA are failure; 3.8–20.5 mA is valid measurement information; 3.8–4 and 20–20.5 mA is the saturation (over/under-range) zone; the gaps 3.6–3.8 and 20.5–21 mA are undefined. Devices output their failure current according to their own configuration, so confirm in your device manual. Sources: Beckhoff NAMUR information, Vaisala documentation.
- Inputs are processed in your browser and are not sent anywhere.