The biggest advantage of 4-20 mA is that it can tell “the measurement is zero” apart from “the line is broken”. But this advantage does not work by itself: if nobody checks the raw value in the PLC program, a broken wire keeps showing on the screen as “zero pressure”. This post covers two jobs together: reading NAMUR NE43 fault levels and scaling the raw number correctly to an engineering unit.
What does NAMUR NE43 say?
NE43 is a NAMUR recommendation that describes which current range in a 4-20 mA loop counts as measurement information and which counts as fault information. Documents from manufacturers such as Beckhoff, Vaisala and JUMO present NE43 as follows:
| Current range | Meaning |
|---|---|
| 3.8 - 20.5 mA | Valid measurement information (including overrange margins) |
| 3.6 mA and below | Fault information (low) |
| 21 mA and above | Fault information (high) |
The text of the standard itself is paid, and this post does not rely on it word for word; the table gives the values that manufacturer documents report. What matters is this: in real transmitters the fault current is adjustable and differs by manufacturer. Some devices set the high alarm to a value such as 22 mA, others pull the low alarm to 3.5 mA or lower. So do not memorize 3.6 and 21 mA; read the fault current setting in your transmitter’s datasheet and set the PLC thresholds accordingly.
One more point to clarify: a broken wire does not mean the transmitter produces its own fault current. When the loop breaks, the current drops to 0 mA; this falls into NE43’s low fault region, but the transmitter’s “own fault” and a wire break get mixed into the same number. For the PLC, both lead to the same conclusion: the measurement is not reliable.
From raw value to engineering unit
The analog card converts current into a number. In the Siemens S7 family, the nominal range for current inputs is defined as 0 - 27648 (a reply on the Siemens support forum bases this range on the system manual). What follows depends on the card and its parameter settings:
- If the channel is set to the 4-20 mA range, 4 mA generally corresponds to 0 and 20 mA to 27648.
- If the channel is set to the 0-20 mA range, 4 mA is approximately 5530 (calculation: 4/20 x 27648 = 5529.6).
Which one applies is written in the card’s range parameter and the module manual; mixing the two up is the most common scaling error in the field. The general formula is:
Eng = EngMin + (Raw - Raw4mA) / (Raw20mA - Raw4mA) x (EngMax - EngMin)
Example: a 0-10 bar transmitter, card in 4-20 mA mode. For 12 mA the raw value is 13824, and (13824 - 0) / (27648 - 0) x 10 = 5 bar. If you read the same transmitter in 0-20 mA mode, 12 mA is approximately 16589; put 5530 and 27648 into the formula and you again get 5 bar. So the numbers change, the formula does not; only the lower and upper raw values are chosen according to the card mode.
The table below is our own calculation (based on 27648); confirm it from the manual for your module family:
| Current | Raw (4-20 mA mode) | Raw (0-20 mA mode) |
|---|---|---|
| 3.6 mA | approx. -691 | approx. 4977 |
| 3.8 mA | approx. -346 | approx. 5253 |
| 4 mA | 0 | approx. 5530 |
| 20 mA | 27648 | 27648 |
| 20.5 mA | approx. 28512 | approx. 28339 |
| 21 mA | approx. 29376 | approx. 29030 |
In 4-20 mA mode it is possible to see a negative raw value; define the variable as a signed integer (Int), because if you define it as unsigned, the underflow turns into a wrong large number. The limits of the overrange and underrange regions, and the number the card returns on a wire break, vary by module; sources contradict one another on this. Instead of memorizing the break value, deliberately open the channel during commissioning to test it and record the raw value.
Generating a fault bit in the PLC
Do not rely on card diagnostics alone. A simple and portable approach:
- Convert the thresholds from current to raw values yourself (according to the transmitter’s fault current setting).
- Set the
Faultbit when the raw value goes below the lower threshold or above the upper threshold. - Add a short delay so that momentary spikes do not raise false alarms; the duration is determined by the process.
- While a fault is present, do not feed the scaled value into the control logic: hold the last valid value or put the output in a safe state.
- Send the fault to SCADA as a separate alarm; show “measurement faulty” instead of “0 bar”.
Common mistakes
- A mismatch between the card’s range parameter and the lower raw value in the scaling formula.
- Treating the NE43 thresholds as fixed numbers and not reading the transmitter’s actual alarm current.
- On a wire break, the scaled value silently showing 0 and entering the control logic.
- Keeping the raw value in an unsigned variable.
- Commissioning without testing a wire break.
Commissioning checklist
- Has the card range (4-20 mA / 0-20 mA) been determined and confirmed from the module manual?
- Are the lower/upper raw values in the scaling formula based on this range?
- Has the transmitter’s fault alarm current setting been read from the datasheet?
- Are the lower and upper fault thresholds defined in the PLC as raw values?
- Was a wire break deliberately created and the raw value returned by the card recorded?
- Does the control logic behave safely at the moment of a fault?
- Does the measurement fault appear as a separate alarm in SCADA?
- Is the raw value variable a signed integer?
To try your own values, you can use the 4-20 mA and PLC raw value scaling calculator; you enter the raw range, and you should verify the result against the device documentation.
To set up the thresholds, scaling range and fault behavior correctly for each project, take a look at our Industrial automation page.