Analog Measurement Chain: Sensor to SCADA Scaling

Guide to sensor selection, accuracy, 2-3-4 wire, 4-20 mA voltage budget, shielding, isolation, ADC, scaling, filtering, alarms, error budget and loop check.

Published: · Author: Mekatrio team

A pressure, temperature or level value on the screen is not the product of a single part. The sensor, transmitter, cable, input card, PLC code and SCADA scaling are links lined up one after another, and each link adds its own error. The weakest link in the chain is often not the most expensive device. A wrong scaling constant or a wrongly grounded shield can waste the accuracy of a good transmitter.

This guide treats the chain from start to finish as a single flow. You can find signal type selection (4-20 mA or 0-10 V?) and the basics of wire break and scaling (NE43 and PLC analog scaling) in our published notes. We do not repeat them here. We connect those topics to the rest of the chain and add the missing links such as error budget, filtering, alarms and calibration.

Contents

  1. Measurement requirement and sensor selection
  2. Accuracy, repeatability and resolution
  3. Sensor connection: 2, 3 and 4 wire
  4. 4-20 mA loop voltage budget
  5. Limits of a 0-10 V input
  6. Cable and shield
  7. Isolation
  8. PLC analog input and ADC resolution
  9. NAMUR NE43 and fault handling
  10. Scaling: from PLC to SCADA
  11. Filtering
  12. Alarm thresholds
  13. Error budget
  14. Calibration and loop check
  15. Design and commissioning checklist
  16. Frequently asked questions

1. Measurement requirement and sensor selection

Sensor selection starts not with the catalog but with the question of what the measurement is for. The same pressure point creates different requirements in a process control loop, an energy calculation or a protection interlock.

Answer these questions first

  • What will the measurement be used for? Indication, control (PID), alarm, interlock or reporting. Interlock and protection functions need a separate and stricter design; this guide does not cover them.
  • What is the real operating range? The normal operating value, the highest expected value and overload (for example the pressure surge when a valve closes).
  • What accuracy is really needed? Accuracy tighter than needed comes back as cost and maintenance load.
  • What is the environment? Temperature, vibration, humidity, corrosion, explosive atmosphere, hygiene requirements.
  • What should the response time be? A fast pressure control and a tank level do not need the same response time.
  • What should the output type be? 4-20 mA, 0-10 V, digital communication or a direct sensor input (RTD, thermocouple).

Choose the measuring range close to the need

Choosing a range wider than necessary is a typical mistake. If you monitor a 0-6 bar process with a 0-100 bar transmitter, both the transmitter accuracy (usually given as a percentage of the range) and the ADC resolution operate on a slice that is insufficient for those 6 bar. On the other hand, if you choose the range too narrow, the sensor saturates when the process overshoots and may be damaged. The solution is to keep the normal operating point in the middle region of the range and the overload limit below the sensor’s withstand value. For withstand and overpressure values, see the manufacturer’s documentation.

Direct sensor or transmitter?

Sensors such as RTDs or thermocouples can be connected directly to the PLC card. In that case the card must support the sensor type and connection method. The alternative is to put a temperature transmitter at the sensor and convert it to 4-20 mA. Because the transmitter is close to the sensor in the field, you do not have to carry the measurement signal over a long distance at a weak level. In return, one more device is added and the maintenance scope grows. Make the choice according to distance, ambient noise and card support.

For the standard curves of sensor types (for example IEC 60751 for Pt100, IEC 60584 for thermocouples), confirm the current version and tolerance classes from the relevant standard text.

2. Accuracy, repeatability and resolution

These three concepts are often confused in the field and used interchangeably. Yet they describe different things.

Concept What it describes Result in the field
Accuracy How close the measured value is to the true value How far the indication deviates from what is real
Repeatability How close repeated measurements under the same conditions are to each other Does it give the same value when it comes back to the same point
Resolution The smallest step the measurement chain can distinguish Whether you can see small changes

They are independent of each other

A system with high resolution does not have to be accurate. A 16-bit card reads a transmitter with a drifted offset wrongly in very fine steps. Conversely, an accurate but low-resolution system may not see a small deviation. In a control loop, repeatability and resolution are usually more decisive than absolute accuracy, because PID catches small differences. In applications where the absolute value matters, such as reporting and billing, accuracy comes to the fore.

Pay attention to how the accuracy value is given

Manufacturers give accuracy on different bases: percentage of the measuring range (% span), percentage of the reading (% reading) or a combination of them. In addition, the accuracy definition sometimes covers only linearity, hysteresis and repeatability; temperature effect, long-term drift and mounting position are written on separate lines. When comparing two transmitters, compare them on the same base and with the same scope. If the scope is unclear, confirm it from the manufacturer’s documentation.

Stability (drift) is also an error

Sensors drift over time. A transmitter calibrated a year ago may not have the same accuracy today. The drift values are in the datasheet; set your calibration interval according to this value and the criticality of the process.

3. Sensor connection: 2, 3 and 4 wire

In the 4-20 mA and 0-10 V article we covered the 2/3/4-wire power connection of the transmitter. Here the same term has a second meaning: the measurement connection of resistance sensors (RTD). Do not confuse the two; one describes the energy type of the transmitter, the other how the sensor’s cable resistance is handled.

Why does the number of wires matter for an RTD?

The resistance of an RTD such as a Pt100 changes in very small steps with temperature. The resistance of the cable itself is added directly to this measurement and read as temperature.

  • 2-wire: The cable resistance is added in series with the sensor resistance and cannot be separated. It is acceptable over short distances and with low accuracy requirements. As the cable gets longer and the ambient temperature changes, the error grows.
  • 3-wire: The third wire makes it possible to measure and compensate the cable resistance. This method assumes that the resistances of the two wires are equal. It is a commonly used choice in the field.
  • 4-wire: Current and voltage are measured with separate wires; the effect of the cable resistance is largely eliminated. It is preferred where high accuracy is needed.

Which connection type the card supports and how to use the terminals is written in the card manual. Do not wire by guess; a wrongly connected 3-wire sensor often gives a value that looks reasonable but is wrong.

Solving the wire-count problem with a transmitter

If you connect the sensor to a temperature transmitter in the field and make the output 4-20 mA, the sensor’s short cable stays at the transmitter end and the current loop carries the long distance. This practically eliminates the RTD cable resistance problem over long distances.

4. 4-20 mA loop voltage budget

The current in the loop is the same along the cable; but the supply voltage drops by some amount across every element in the loop. If the supply cannot cover the sum of these drops, the transmitter does not receive enough voltage and the signal chokes at high current values.

Basic budget

V_supply(min) ≥ V_transmitter(min) + I(max) × (R_cable + R_shunt + R_other)
  • V_transmitter(min): The lowest terminal voltage required for the transmitter to operate (datasheet).
  • I(max): The highest loop current you must account for. It should not be 20 mA, but the highest value in the datasheet, including the transmitter’s fault alarm current, because the loop is expected to work during a fault as well.
  • R_cable: The total resistance of the outgoing and return wires. Count both directions, not one.
  • R_shunt: The internal resistance of the input card or an external shunt.
  • R_other: Series-connected indicators, isolators, barriers.

Example calculation (general values, for illustration)

The numbers below do not belong to a real device; they were chosen to show the method. Recalculate with the values of your own device.

Item Example value
Supply 24 V
Transmitter minimum voltage 12 V
Loop current (highest) 22 mA
Cable (outgoing + return) 100 Ω
Shunt / input resistance 250 Ω

The loop resistance is 350 Ω, the voltage drop 22 mA × 350 Ω = 7.7 V. Together with the transmitter’s requirement that is 19.7 V, leaving a margin of about 4.3 V with a 24 V supply. Anything that consumes this margin (a long cable, an extra indicator, a barrier) requires the calculation to be redone.

Common reasons the budget is broken

  • Counting only one direction of the cable resistance.
  • Forgetting the series resistance of elements such as an Ex barrier or an isolator.
  • Not accounting for the supply voltage working at the lower tolerance limit (for example a low 24 V inside the panel).
  • If the transmitter uses communication such as HART, skipping the minimum loop resistance requirement. Read this from the transmitter’s documentation as well.

Active/passive input compatibility is part of the budget: who provides the supply and which voltage enters the calculation depend on it. Confirm the card and transmitter wiring diagram from the datasheets.

5. Limits of a 0-10 V input

0-10 V works over short distances and for non-critical measurements. Knowing its limits determines where you can use it.

Weak points of a voltage input

  • High input impedance: Noise coupled capacitively and inductively onto the line is added directly to the measurement.
  • Cable resistance and load effect: The source output impedance and the cable resistance form a voltage divider with the input impedance. With a card with low input impedance, or an output connected in parallel to several receivers, this effect turns into error.
  • Common ground problem: The ground potential difference between source and receiver is added directly to the signal.
  • No live zero: 0 V is both a valid value and possibly a broken line.
  • Above range: Some cards can read a little above 10 V; this varies by card and module and must be confirmed from the manufacturer’s documentation.

Practical rule

If you will use 0-10 V, keep the distance short, use shielded twisted pair, check the source’s output load limit (minimum load resistance) and keep the number of receivers below the datasheet limit. Do not use 0-10 V in a measurement where a cable break matters for safety.

6. Cable and shield

A good transmitter gives a bad measurement with a bad cable. Cable selection and routing are the cheapest and most lasting component of measurement quality.

Cable type

  • Twisted pair: Noise couples equally onto the two wires and cancels out at the differential input. It is a basic requirement for analog signals.
  • Shield: Provides protection against external electrical fields. Foil shields and braided shields behave differently in different frequency ranges; see the cable manufacturer’s definition.
  • Multi-pair cables: When carrying several analog pairs in one cable, having the pairs individually shielded reduces crosstalk between channels. Do not mix analog and digital signals in the same cable.

Routing

  • Run analog cables on a route separate from motor output cables, frequency converter outputs and high-current power cables.
  • If crossing is unavoidable, cross at a right angle.
  • Use a separate compartment or a separate duct inside the cable duct.
  • For the minimum distance between power and signal cables, see the panel design standards and the cable manufacturer’s recommendation; this guide does not give a fixed distance. For in-panel layout, take a look at the control panel design standards guide.

Shield grounding

Where and at how many points the shield should be grounded is one of the most debated topics in the field. The general practice is to ground the shield at one end; however, high-frequency interference and different plant conditions may require other solutions. For details and alternatives, see our shield grounding note. Let us add only this: also monitor the shield for continuity. A shield that breaks in terminals and junction boxes can remain a hidden problem in the measurement for years.

Junction boxes and terminals

Every additional connection point is a candidate for faults and noise. Reduce junction boxes; if they must be used, keep signal and power pairs in separate terminal groups, keep the shield continuous and match terminal labels with cable labels.

7. Isolation

Isolation controls ground loops and common-mode voltages in the measurement chain. It also limits field voltage reaching the PLC logic side in the event of a fault.

Which isolation where?

  • Channel-to-channel isolation: Each analog input is electrically separate from the others. It matters if you connect transmitters powered from different sources to the same card.
  • Field-to-logic isolation: The field side of the input card is separate from the PLC internal logic/bus side.
  • External signal isolator: An independent device inserted when the card’s isolation is insufficient or the signal source is at a different potential.

What does isolation solve, and what does it not?

Isolation cuts currents caused by ground potential differences and common-mode voltages. However, it does not on its own solve noise coupled capacitively or inductively onto the cable; cable type and routing are needed for that. The withstand voltage and common-mode range of isolation are also not unlimited; compare the values in the card and isolator datasheet with your design voltages.

Practical warnings

  • If you connect several transmitters to a non-isolated (common-reference) input, check by drawing how the transmitters’ references are connected to each other. An unexpected path can cause the loop current to return through another channel’s path.
  • For 4-wire transmitters, read from the manual whether the supply negative terminal and the signal common are connected internally.
  • On long or outdoor lines that need lightning and overvoltage protection, treat the selection of the protective element as a separate design item.

8. PLC analog input and ADC resolution

The analog card converts current or voltage into a number. How many steps this number consists of and how fast it is produced determine the usability of the measurement.

Bit count and step

An N-bit ADC divides the input range into 2^N steps. 12 bit means 4096 steps, 16 bit means 65536 steps.

Example (general, for illustration): if the entire 0-10 bar measuring range is spread over 12-bit resolution, one step is about 2.4 mbar. How much of the card resolution is actually used in the 4-20 mA range depends on the card’s range setting; so do the calculation with the value in your own card’s manual.

Bit count is not real accuracy

A card saying “16 bit” does not mean the measurement has 16-bit accuracy. Manufacturers also give an accuracy (usually % span, with a temperature coefficient) and a noise value. The effective resolution is often lower than the nominal bit count because the lower bits are lost in noise. Make the comparison on the card’s total error value instead of the bit count.

Conversion time and scan

The card may read channels sequentially or in parallel. The conversion time per channel, the number of enabled channels and the on-card filter setting determine the update time. Disabling channels you do not use may shorten the update time (confirm from the card manual). If the update time is longer than the PLC scan time, you see the same measured value in more than one scan; this is normal but must be taken into account for a fast loop.

Mains frequency setting

Many cards have an integration time or mains frequency rejection setting. Since your mains frequency is 50 Hz, check in the manual whether the card’s default setting suits this frequency. The choice between a fast, noisier setting and a slow, quieter setting is made according to the speed requirement of the process.

Range parameter

The card’s input range (4-20 mA, 0-20 mA, 0-10 V, ±10 V, etc.) is selected by a software parameter or a hardware switch. The scaling formula depends on this choice; you can find the details in the NE43 and PLC scaling note. A mismatch between the parameter and the wiring (for example connecting current in voltage mode) can cause more than a measurement error: hardware damage.

9. NAMUR NE43 and fault handling

NE43 is a NAMUR recommendation that separates measurement information from fault information in a 4-20 mA loop. As we covered in the published note, manufacturer documents give the valid measurement range as about 3.8-20.5 mA and the fault zones as about 3.6 mA and below and 21 mA and above. Since the standard text is paid, confirm these values for your own device from the manufacturer’s documentation and the current NE43 text.

What does it mean for the chain?

  • The fault current is a setting of the transmitter; your PLC thresholds must match this setting.
  • A broken cable affects the raw value the card returns differently depending on the module. At commissioning, deliberately open the loop and record the value.
  • Fault information should be carried as a separate signal from the measured value (measurement quality). We combine this with scaling in the next section.

Use the overrange zone

The narrow zones outside the measuring range (for example 3.8-4 mA and 20-20.5 mA) indicate that the sensor has gone out of range. Evaluating this information as a “range exceeded” warning reveals both process overflow and sensor range selection errors.

10. Scaling: from PLC to SCADA

The raw number is converted to an engineering unit, then this value is carried to SCADA. The most common mistake is scaling in two places or not documenting it at all.

Scale in one place

Do the scaling in the PLC, send the value in engineering units to SCADA and do not apply a second scaling in SCADA. Scaling in two places leads to one being updated and the other forgotten during a change. On the SCADA side only display ranges (trend axis, bar chart limits) are defined.

Keep scaling parameters as data

Low and high engineering values, low and high raw values and fault thresholds should be defined as parameters, not as constants embedded in the code. The same function block can be used on different channels and a change is made in one place.

Example measurement record (general example)

The table below shows the format of a tag list. The names and values are examples; they do not belong to a real plant.

Example tag Description Range Unit Input type Fault low / high threshold
EXAMPLE_PRESSURE_01 Example pressure measurement 0 - 10 bar 4-20 mA From the transmitter datasheet
EXAMPLE_TEMPERATURE_01 Example temperature measurement 0 - 150 °C 4-20 mA From the transmitter datasheet
EXAMPLE_LEVEL_01 Example level measurement 0 - 100 % 4-20 mA From the transmitter datasheet

Every measurement should be carried with two values

  1. Value: The scaled number in engineering units.
  2. Quality/status: Fault, range exceeded or valid information.

SCADA should show these two together. In a fault, the old value silently freezing on the screen or showing 0 misleads the operator. Showing the value with a different appearance (gray, dashes, “bad”) and raising an alarm when the quality bit is bad is the last link of the measurement chain.

Scaling overflow and type errors

  • Keep the raw value in a signed integer; negative values can occur.
  • Integer division in an intermediate calculation causes truncation in small ranges. Do the scaling calculation with a real number (floating point).
  • Add a guard in the division against the possibility that the low and high raw values are equal.

11. Filtering

A filter reduces noise but adds delay. There is a trade-off between the two, and the right place depends on the dynamics of the process.

Where to filter?

  • On-card filter: Comes with the card settings; there are integration time and averaging options. See the card manual.
  • In-transmitter damping: Many transmitters offer an output damping time setting.
  • PLC software filter: Moving average or first-order filter.

Filtering the same signal in three places increases the total delay without being noticed. Record the setting at each layer and calculate the total delay.

First-order filter

A simple and common method:

Y_new = Y_old + α × (X - Y_old)
α = Ts / (Tf + Ts)

Here Ts is the sampling period and Tf is the filter time constant. As Tf grows, noise decreases and the response slows down. The time constant must be kept clearly shorter than the fastest meaningful change in the process; the exact ratio is determined according to the project.

Do not confuse the filter with diagnostics

Do the fault (break, range exceeded) check on the unfiltered raw value. A filter can smooth out a short break pulse. The alarm delay is defined separately and deliberately; it is not left as a side effect of the filter.

A filter hides the cause of noise

If the noise is high, first look for its cause: shield, grounding, isolation, routing. A software filter covers up these problems but does not solve them. Use the filter as fine tuning after the problem is solved.

12. Alarm thresholds

The alarm is where the measurement turns into something for the operator or the control logic. Badly set up alarms either never sound or sound constantly and are ignored.

Alarm types

  • Measurement fault: Break, range exceeded, invalid value.
  • Process alarm: Low-low, low, high, high-high.
  • Rate-of-change alarm: The value changing too fast (for example a sudden pressure drop).

Threshold, hysteresis and delay

  • Hysteresis (dead band): Prevents the alarm from constantly setting and clearing when the value oscillates right around the alarm threshold. The hysteresis value must be larger than the measurement noise.
  • Delay (on-delay): Prevents short-lived temporary deviations from producing an alarm. The time is set according to the process; for a safety-critical alarm, evaluate the effect of the delay separately.
  • Priority: Not every alarm has the same importance. Separate those the operator must act on immediately from those that only inform.

Relate thresholds to measurement uncertainty

If you set the alarm threshold right above the process limit, because of measurement error the alarm may be late when the real value has exceeded the limit, or may sound while it is below the limit. Leave a margin between the threshold and the real limit that covers your error budget. This is the subject of the next section.

Suppress the process alarm during a fault

Producing a “low pressure” alarm while the measurement is faulty gives wrong information. In a fault, suppress the process alarms and show a single “measurement fault” alarm. In the control logic too, decide whether a faulty measurement holds its last valid value or goes to a safe state; this decision depends on process risk and must be written explicitly in the design.

13. Error budget

An error budget adds up the contribution of every link in the chain and tells you how reliable the value on the screen is.

Error sources

Link Typical error sources
Sensor / transmitter Accuracy, temperature effect, drift, mounting position
Shunt / signal conversion Resistor tolerance and temperature coefficient
Cable Noise, shield problems, ground loop
Input card Accuracy, offset, temperature coefficient, resolution, noise
Software Scaling parameters, filter delay, type errors

Two methods of summing

  • Worst case (arithmetic sum): Assumes all errors are in the same direction and at their largest value. Safe but pessimistic.
  • Root sum of squares (RSS): Adds assuming the errors are independent. Gives a realistic estimate. Also read the guide text (GUM) on which the method used for measurement uncertainty is based, and confirm the coverage factor there.

Example calculation (general values, for illustration)

Take the errors of four links as 0.25, 0.10, 0.10 and 0.05 in % span. The arithmetic sum is 0.50 %. The root sum of squares is about 0.29 %. These values do not belong to a real device. Recalculate the result with your own datasheet values and keep it in a spreadsheet.

How to use the budget

  1. Determine the accuracy required (alarm margin, control sensitivity, reporting).
  2. Take each link’s error contribution from the datasheet.
  3. Calculate the total and compare it with the requirement.
  4. If it exceeds the limit, improve the link that contributes the most. That link is sometimes not the most expensive device. For example it may be a device with a wider range than necessary or one that has not been calibrated for a long time.

Datasheet accuracy values are valid under certain reference conditions. If the ambient temperature is different, add the temperature coefficients to the budget as well.

14. Calibration and loop check

Calibration finds what the sensor or transmitter shows against a reference and adjusts it if necessary. A loop check verifies that the signal follows the correct path from the field to SCADA. They are different jobs.

Calibration

  • “As-found” first: Record the existing error before making an adjustment. This shows how far the device drifted within the calibration interval.
  • Multiple points: Not only the end points but also intermediate points are checked; for example 0%, 25%, 50%, 75% and 100% of the range, in both rising and falling directions. The difference between falling and rising direction shows hysteresis.
  • Then “as-left”: Record the values after adjustment.
  • Reference device: The uncertainty of the reference you use must be clearly smaller than that of the device under test. Follow your organization’s or accreditation requirements on this ratio.
  • Record: Reference device ID, date, ambient condition, result and the person who did it are recorded.

Loop check

A loop check verifies the whole path starting from the sensor end in the field up to the operator screen.

  1. Simulate the transmitter or connect a current source to the loop and apply points such as 4, 12 and 20 mA (or 0%, 50%, 100%). The connection point and method must be chosen so as not to disturb the loop.
  2. Read the raw value and the scaled value in the PLC.
  3. Compare the value, unit and display format in SCADA.
  4. Trigger the alarm thresholds in the upward and downward directions; check that the alarm text, priority and log are correct.
  5. Create a cable break deliberately, record the raw value the card returns and the fault bit; a measurement fault must appear in SCADA.
  6. Apply the overrange zones (low and high).
  7. Enter the results in a signed table against the tag list.

The loop check is part of the FAT and commissioning checklists; for an example list, see the FAT checklist note.

Calibration interval

The interval is determined according to the device’s drift value, the criticality of the process and past “as-found” results. We do not give a fixed period; it is defined according to the project and the quality system.

15. Design and commissioning checklist

  • Was the purpose of the measurement (indication, control, alarm, reporting) defined?
  • Was the measuring range selected according to normal operation and overload conditions?
  • Were accuracy, drift and temperature effect taken from the datasheet?
  • Is the RTD connection type (2/3/4 wire) compatible with the card and sensor?
  • Was the 4-20 mA loop voltage budget calculated for the highest current and the lowest supply?
  • Where 0-10 V is used, are the distance, load and noise conditions suitable?
  • Was twisted pair, shielded cable selected and a route separate from power cables planned?
  • Was the shield grounding method determined and carried into the implementation?
  • Was the isolation need (channel, field-to-logic, external isolator) evaluated?
  • Were the card range, resolution, filter and mains frequency setting confirmed from the manual?
  • Are the transmitter’s fault alarm current and the PLC fault thresholds compatible?
  • Is scaling done in one place and are parameters kept as data?
  • Are value and quality information carried to SCADA together?
  • Are the filter settings (transmitter, card, software) recorded and is the total delay known?
  • Were alarm thresholds set together with hysteresis, delay and measurement uncertainty?
  • Was the error budget calculated and compared with the requirement?
  • Were calibration (as-found/as-left) and the loop check done and the records kept?
  • Were cable break and range exceeded tested deliberately?

16. Frequently asked questions

At what stage should I do the error budget?

Before sensor selection. Selecting without knowing the required accuracy leads either to an unnecessarily expensive or an insufficient device. Review the budget again at commissioning.

Is a 16-bit card always more accurate than a 12-bit card?

No. Resolution, accuracy and noise are separate values. Make the comparison on the card’s total error value.

How long should I keep the filter time?

It depends on the dynamics of the process. It should be clearly shorter than the fastest meaningful change, and the total delay (transmitter, card, software) should be evaluated together. We do not give a fixed time; it is determined according to the project.

Should scaling be done in the PLC or in SCADA?

In the PLC. SCADA receives the value in engineering units and the quality information. Scaling in two places leads to inconsistency.

What should appear on the screen when the cable breaks?

Not “0” or the last value, but a clear “measurement fault” state and an alarm. Since the raw value the card returns on a break varies by module, test this deliberately at commissioning.

Are a loop check and calibration the same thing?

No. Calibration checks the accuracy of the device, while the loop check checks the correctness of the signal path (wiring, card, scaling, SCADA tag, alarm). One cannot replace the other.

How long should the calibration interval be?

It is determined according to the device’s drift value, the criticality of the process and previous “as-found” results. We do not give a fixed period; define it according to the project and the quality system.

Can I write the NE43 values into the PLC as constants?

As a starting point yes, but read the transmitter’s actual fault current setting from the datasheet and update the thresholds accordingly. For current values, confirm from the NE43 text and the manufacturer’s documentation.


For deviation, noise or scaling problems in an existing measurement line, or to design the chain of a new line from scratch, take a look at our Industrial automation page.

Tags

  • analog measurement
  • measurement chain
  • 4-20 mA
  • PLC analog input
  • calibration