Anyone looking for a one-sentence answer to “is the shield grounded at one end or both?” finds contradictory advice, because the answer depends on the signal the cable carries. This post summarizes what manufacturer documents say for three cable types commonly met in field and panel practice, and where to be careful.
What does the shield do, and why are the two ends disputed?
The shield stops the electric field outside the cable from coupling into the inner conductors. To work, it has to be connected somewhere. The dispute comes from this: if the two ends are at different ground points, there can be a potential difference between them; if the shield is connected at both ends, this difference drives current through the shield, and that current can couple into the signal pair as noise. On the other hand, a shield connected at one end cuts off only certain types of interference. ABB’s PLC help page says this explicitly: grounding at one end protects only against capacitively coupled interference and low-frequency disturbances such as 50 Hz; the same page recommends grounding the shield at both ends for general data cables and at one end for small analog signals. For lines that have a specification, such as Modbus, the specification’s own description takes precedence (see below).
So there is no single rule; the decision is made by cable type.
Summary by cable type
| Cable | General approach | Basis / note |
|---|---|---|
| Small analog signal (4-20 mA, thermocouple, Pt100) | Generally at one end, mostly at the panel/PLC side | ABB help page; if the manufacturer’s manual says otherwise, that applies |
| Modbus RTU (RS-485) | Shield to protective earth at one end; the common (reference) conductor at a single point for the whole line | Modbus over Serial Line V1.02, Sections 3.4.4 and 3.6 |
| Drive motor cable | Shield at both ends, with 360° contact | ABB EMC and grounding guides |
The word “generally” in the table is important; do not apply a general rule that conflicts with your device’s installation manual.
Analog signal cable
Choose twisted-pair, shielded cable and run it in a separate duct from power and motor cables. Ground the shield generally at the PLC/panel side; at the field end leave the shield insulated and terminate it, or follow the device manufacturer if it asks for something else. Keep shield continuity in intermediate terminal boxes but do not connect it to the box enclosure; otherwise you create a second ground point unintentionally.
In plants where the ground potential difference is large, using galvanic isolation is a more robust solution than trying to fix the shield arrangement: the isolator separates the ground of the signal source from the ground of the input card.
Modbus RTU / RS-485 line
The Modbus over Serial Line specification calls for a shielded cable and describes connecting the shield to protective earth at one end. In addition, the communication reference (common) is the third conductor that joins all devices, and it is connected to protective earth at a single point for the whole line (usually at the master side). Practical consequences:
- Do not connect the shield to the enclosure of every device; if each device is inside a grounded panel, many ground points form along the chain.
- Do not ground the common in more than one place.
- If the ground potential difference is large, plan an isolated transceiver or an external isolator.
Drive (VFD) and motor cables
The drive output generates high-frequency noise. ABB’s grounding and cabling guides recommend terminating the shielded motor cable with 360° contact both at the cabinet entry and at the motor terminal box; instead of connecting the shield with a long wire (a “pigtail”), use an EMC gland or a wide-surface clamp. The one-end rule for low frequency does not apply here, because the goal is not only 50 Hz interference but returning the high-frequency current to its source. Cable separation distances and length limits are determined by the drive manufacturer’s manual; do not rely on a generic figure.
Common mistakes
- Unintentionally grounding the same shield at both the panel side and the field side (for example through a terminal box enclosure).
- Connecting the shield at the cable end with a long wire and losing its effect at the drive side.
- Breaking shield continuity at intermediate terminals.
- Running analog and drive cables side by side in the same duct.
- Not using the common conductor at all on a communication line, or grounding it at more than one point.
- Trying to solve a ground loop with one-end grounding while leaving untouched the actual problem, the ground potential difference.
Checklist
- Has the shield strategy (one end / both ends / 360°) been set in writing for each cable type?
- Has the shield recommendation in the device manufacturer’s installation manual been read?
- In intermediate terminal boxes, is shield continuity present but insulated from the enclosure?
- On the RS-485 line, are the common and the shield grounded at a single point?
- On the drive motor cable, is 360° contact provided at both ends?
- Are analog, communication and power/motor cables on separate routes?
- Is isolation planned on lines where a ground potential difference may exist?
- After commissioning, was noise observed and were the shields checked?
To plan the cable routing, shield termination and grounding arrangement for your project, take a look at our Industrial automation page.