4-20 mA or 0-10 V? Choosing an Analog Signal

Choosing between 4-20 mA and 0-10 V: a field guide to live zero, noise, cable length, shunts, 2/3/4-wire, wire breaks and common mistakes.

Published: · Author: Mekatrio team

When you buy a transmitter, a valve positioner or a frequency converter, the same question comes up: should the analog signal be 4-20 mA or 0-10 V? The catalog lists both, and the PLC card reads both. The difference shows up once you are in the field: when the cable gets longer, when a motor cable runs past the panel, or when a wire breaks.

The basic difference: is the signal current or voltage?

0-10 V is a voltage signal. The receiving input has high impedance, so noise on the line and cable resistance feed directly into the measurement. 4-20 mA is a current loop: the current is the same along the whole line, the receiving input has low impedance, and interference voltage coming from outside affects the measurement much less.

Live zero

On 4-20 mA, the sensor outputs 4 mA at the bottom of the measuring range and 20 mA at the top. So a “zero value” can be told apart from a “broken line”: if you see 0 mA, the sensor is not measuring zero, the loop is broken. On 0-10 V, 0 V can be both a valid measurement and a broken cable; you cannot tell them apart.

Noise immunity

Motors, conveyors, frequency converters and radio transmitters disturb voltage signals. A current loop working with a low-impedance input is more resistant to this kind of interference.

Cable length

A voltage signal loses accuracy in the cable resistance. In a current loop, the current stays the same along the cable, so cable resistance does not corrupt the measurement; it only uses up part of the supply voltage margin. That is why 4-20 mA is the natural choice over long distances.

Comparison table

Feature 4-20 mA 0-10 V
Wire break Detected (0 mA is invalid) Indistinguishable (0 V may be valid)
Noise immunity High (low-impedance input) Weaker
Long cable Suitable Loss of accuracy
Effect of cable resistance Does not corrupt the measurement, uses up supply margin Goes directly into the error
Number of connections 2-wire loop possible Separate supply needed
Installation effort Requires supply margin and active/passive compatibility calculation Simple, practical over short distances

250 ohm shunt: converting current to voltage

If you need to connect a 4-20 mA signal to a device with a voltage input, a shunt (burden) resistor is placed in the line. 250 ohm is the common reference value: 250 ohm x 20 mA = 5 V, so a 4-20 mA signal becomes 1-5 V. Some application notes use 249 ohm; the difference comes from the choice of standard resistor value. Choosing a precise (low-tolerance) shunt directly affects measurement error.

2-, 3- and 4-wire connections

  • 2-wire (loop-powered): The supply, the transmitter and the measuring input are connected in series; the same two wires carry both power and signal. This is the most common type in the field.
  • 4-wire: Power and signal are separate connections. Because power is separated from the measurement system, the isolation requirement on the receiving side is reduced; the cost is that the power pair also has to be run over the whole distance.
  • 3-wire: The definition can vary from manufacturer to manufacturer. For this type, confirm which terminal is the common from the device manual; do not wire it by guessing.

Active/passive input compatibility

This is the most commonly confused point: does the PLC analog card supply its own 24 V to the loop (active input), or does it read an externally powered loop (passive input)? If both sides supply power, or neither does, the loop does not work. The correct wiring diagram is in the datasheets of the card and the transmitter; do not find it by trial and error.

Supply margin

The supply voltage must cover the sum of all voltage drops in the loop: the transmitter’s minimum operating voltage, cable resistance, the shunt, and any additional indicators. In one application example, the transmitter worked in the 12-30 V range; once the cable and shunt were taken into account, 17 V was insufficient and 24 V was found suitable. There is no general “maximum loop resistance” figure; it varies per transmitter, so check its datasheet.

Wire-break detection and NAMUR NE43

The biggest advantage of 4-20 mA can be fault discrimination. NAMUR NE43 is a recommendation that defines current values outside the valid measuring range as fault indications. However, do not memorize these as fixed numbers. Fault alarm currents can differ between devices; read your own transmitter’s fault levels and configuration options from its datasheet. Then generate a fault bit on the PLC side according to those levels.

What an analog card returns when the cable breaks also varies by module. Do not rely on card diagnostics alone: in the PLC code, generate your own fault bit when the raw value falls below the valid range, and put the output into a safe state in that case.

Shield grounding

For analog signals, use shielded twisted-pair cable and route it separately from power cables. The general practice is to ground the shield at one end (usually at the PLC/panel side). If you ground it at both ends, the ground potential difference between the two points drives current through the shield and can corrupt the measurement. If your application requires something different, follow the grounding recommendation of the cable and device manufacturer.

In plants where the ground potential difference is large, galvanic isolation separates the ground of the signal source from the ground of the input card and protects against common-mode voltage.

When is 0-10 V enough?

0-10 V is not a bad choice; it causes problems when used in the wrong place. It makes sense in these cases:

  • The cable is short and inside the same panel or right next to it.
  • There is no strong interference source (motor output cable, contactor), or the routing is separate.
  • A cable break does not affect measurement safety; for example, a speed reference or a setting by potentiometer.
  • The device offers only a voltage input.

If you have a critical process measurement, a long cable or a noisy environment, choose 4-20 mA.

Common mistakes

  1. Active/passive input mismatch: both sides supply power, or neither does.
  2. Grounding the shield at both ends and creating a ground loop.
  3. Not calculating the loop supply margin (long cable, shunt, additional indicators).
  4. Not putting wire-break detection into the PLC software.
  5. Using 0-10 V on a long, noisy line.
  6. Treating NE43 levels as “standard numbers” and not reading the device setting.
  7. Choosing a sensor range much wider than needed and losing resolution.

Selection checklist

  • Are the cable distance and route known, and is it separate from power/motor cables?
  • Are there interference sources (converter, motor, radio) in the environment?
  • Is a cable break critical for the measurement? If so, plan 4-20 mA and a fault bit in the PLC.
  • Is the input card active or passive, and is the transmitter 2-, 3- or 4-wire? Confirmed from the datasheet?
  • Has the supply voltage margin (transmitter + cable + shunt + indicators) been calculated?
  • If a voltage input is required, have the shunt value and tolerance been chosen?
  • Is the shield planned to be grounded at one end only?
  • Has the transmitter’s fault alarm current setting been read from the datasheet?
  • Is the measuring range chosen close to what is needed?

To convert a current or a PLC raw value to an engineering value, there is a 4-20 mA and PLC raw value scaling calculator; verify the result against the device documentation.

Choosing an analog signal often looks like a single decision, but it actually affects the supply, the cable, the grounding and the PLC software together. For a selection specific to your project or for measurement problems on your existing line, see our Industrial automation page.