Level Measurement: Float, Hydrostatic, Ultrasonic

Comparing float, hydrostatic and ultrasonic level measurement for wells and tanks: grease, foam and condensation problems, backup and scaling.

Published: · Author: Mekatrio team

Level is the measurement that decides when pumps start and stop in water and wastewater plants. A wrong or failed level reading runs the pump dry or overflows the well. Even so, sensor selection is often made on “whatever we have at hand.” This article compares the four most common methods for wells, tanks and similar open or semi-open vessels, and covers the questions to ask when choosing.

This is a general framework; it does not recommend a brand or model. Measuring range, accuracy and installation details must be confirmed from the device’s own documentation. Time and cost depend on the project.

1. Why it matters so much

According to the Pumps & Systems article on lift station measurement challenges, wet well level is the most critical measurement at a lift station, because starting and stopping the pumps relies on it. The same article notes that the harsh environment (grease, solids, foam from turbulence, moisture, condensation and sewer gas) strains standard instruments and leads to high failure rates and frequent maintenance.

2. Four methods side by side

Method How it works Strength Watch out for
Float A switch that changes position at a level Simple, decides at a single point Shows only one level point; grease and debris can make it stick
Bubbler Derives level from the air pressure fed into a tube An older continuous method Needs a constant air supply; tubes can clog
Hydrostatic transmitter Submerged, calculates level from water pressure Continuous; a ceramic pressure cell resists abrasion and keeps accuracy despite some buildup Sits in the water; has to be pulled out for maintenance
Ultrasonic Mounted above the well, measures the time of sound reflected from the surface Non-contact Condensation on the sensor face can disturb the signal

The source also notes that larger stations use hydrostatic and ultrasonic instruments together for backup. In newer stations the float often stays as an emergency backup.

Other methods such as radar exist; this article focuses on the methods covered in the source.

3. Environment problems

These headings are common in the source and in the field:

  • Grease and debris. Can leave a float stuck; can build up on the sensor.
  • Foam. Foam forms at a turbulent inlet; non-contact methods may read foam as the surface or lose signal.
  • Condensation. In a humid well the ultrasonic sensor face gets wet. According to the source, self-cleaning sensors boost the signal to shake off the condensate.
  • Inflow. Incoming flow disturbs the surface; the sensor should be moved away from the stream.
  • Dead zone. Ultrasonic sensors have a minimum distance they cannot measure inside; take it from the device documentation and keep the highest level below that limit.
  • Liquid density. Hydrostatic measurement converts pressure to level; if the liquid density changes significantly, the measurement drifts too.

The last two points are general engineering knowledge; confirm details in the device documentation.

4. Selection questions

When choosing a sensor for a well, ask:

  1. Which liquid and environment? Wastewater, drinking water, chemical; is there foam, grease, vapor?
  2. Single point or continuous? Staging pumps usually needs continuous measurement.
  3. Is a backup needed? What happens if the pump runs dry or the well overflows? On important wells, consider a second independent measurement.
  4. Is maintenance easy? If removing the sensor means going down into the well, that affects the maintenance plan.
  5. What is the output signal? Most continuous transmitters give 4-20 mA; the PLC input, cable and wire-break detection are prepared accordingly.
  6. Location? The sensor should be away from the stream, the wall and foamy areas; the device documentation states its mounting requirements.

5. PLC side: scaling and faults

When a continuous transmitter outputs 4-20 mA, the raw number in the PLC is converted to an engineering unit. For example, on a transmitter set for a 0-5 m range, 12 mA is exactly the middle of the range:

level = (mA − 4) ÷ 16 × range = (12 − 4) ÷ 16 × 5 m = 2.5 m

For this calculation to work, the range must be entered the same in the device and in the PLC; if the two differ, the measurement is silently wrong. A wire break or sensor fault can be caught when the signal goes below 4 mA or above 20 mA. For details see NAMUR NE43 and PLC Analog Scaling, for the whole measurement chain see Analog Measurement Chain, and for signal choice see 4-20 mA or 0-10 V?.

For how the level information enters the pump logic, see Pump Station Control Logic: Level and Alternation.

6. Verifying at commissioning

  • Compare the device value with a manually measured level when the well is empty and when it is full.
  • Compare at least one intermediate level too.
  • Break the sensor signal on purpose; see that the PLC raises a fault.
  • Compare the measurement again after some months; you catch drift early.

Checklist

  • Does the environment (grease, foam, condensation) suit the method?
  • Is continuous measurement or a single point needed?
  • Is there a second independent measurement on a critical well?
  • Is the sensor away from the stream and the dead zone?
  • Is the measuring range the same in the device and in the PLC?
  • Is a wire break caught as a separate fault?
  • Was it compared with a manual measurement at commissioning?
  • Is access to the sensor for maintenance planned?