Control panel thermal estimate
Enter the total heat loss inside the panel and the enclosure surfaces exposed to air to roughly see the inside–outside temperature difference. This tool is a preliminary check, not a design approval. Verify with manufacturer data and the relevant standard.
Formulas and assumptions
- Steady-state heat balance:
P = k · A · ΔT. HenceΔT = P / (k · A),Areq = P / (k · ΔTallowed),margin = k · A · ΔTallowed − P. - P: total heat released inside the panel (W). A: outer surface in contact with air (m²). ΔT: difference between internal air and ambient (K).
- Assumptions: sealed enclosure, no fan or air conditioner, indoor location (no solar radiation, not outdoors), internal air treated as a single temperature (in reality the top is warmer), device layout and heat density are ignored.
- Surfaces against a wall or an adjacent enclosure are excluded. The standard method (IEC 60890) uses detailed correction factors for effective area; this tool does not. Confirm details in the standard.
- k value: 5.5 W/m²K is often quoted for painted sheet steel, with different values given for stainless steel and aluminum. Sources are third-party: Industrial Monitor Direct, AutomationDirect selection guide. These sources give a different equation for outdoor use; the tool does not cover outdoors.
- Inputs are processed in your browser and are not sent anywhere.