On a panel project, the question “which standard?” is usually answered with a list. But the documents on that list do not do the same job: some treat the panel as a whole, some its internal devices, some the enclosure, some the machine, and some a market’s or an institution’s own requirements. This article is a map: what each document is about, in which project it comes up, and which misreadings are common in short summaries.
This is general information. Which edition of a standard and which legislation apply to your project follows the contract, the specification and the text in force. Paid standard texts are not reproduced here; no clause numbers or numerical limits are given. For design verification, temperature rise, IP/IK, wiring and FAT details, see our guide Panel Design and Standards: IEC 61439 Guide; we do not repeat them here. This article is not legal or certification advice.
At a glance
| Document | What it is about |
|---|---|
| IEC 61439 series | The panel itself (the assembly) |
| IEC 60204-1 | Electrical equipment of machines |
| IEC 60529 and IEC 62262 | Enclosure protection degrees (IP, IK) |
| IEC 60947 series | The individual devices inside the panel |
| IEC TS 61641 | Internal arc fault protection |
| UL 508A | North American industrial control panels |
| NFPA 79 | Electrical systems of machines in North America |
| TEDAŞ specifications | Utility requirements for network material |
| CE and TSE | Legal conformity and the national standards body |
The IEC 61439 series
The series treats the panel as an “assembly”. Part 1 contains the general rules; it cannot be used alone to specify an assembly or to determine conformity and is applied together with the relevant product part. As of November 2026, the IEC webstore pages show these editions:
| Part | Subject | Edition |
|---|---|---|
| 61439-1 | General rules | 2020 |
| 61439-2 | Power switchgear and controlgear assemblies | 2020 |
| 61439-3 | Distribution boards operated by ordinary persons | 2024 |
| 61439-4 | Assemblies for construction sites | 2023 |
| 61439-5 | Power distribution in public networks | 2023 |
| 61439-6 | Busbar trunking systems | 2012 |
| 61439-7 | Marinas, camping sites, market squares, EV charging | 2022 |
| 61439-8 | Photovoltaic installations | 2026 |
For general-purpose automation and distribution panels, references are usually to 61439-1 together with 61439-2. “Power distribution panel” does not map to a single part: distribution boards operated by ordinary persons fall under 61439-3, and distribution assemblies in public networks under 61439-5. Confirm the current status of the part and edition you will use with IEC, or with the body that publishes the national equivalent (TSE in Türkiye).
The conformity of an assembly is shown through two separate verifications: design verification, and routine verification for each panel. The old distinction between “type-tested” and “partially type-tested” assemblies belonged to IEC 60439 and went away with 61439; testing is only one of the design verification methods. The details are in section 3 of our existing guide.
IEC 60204-1
It gives general requirements for the electrical, electronic and programmable electronic equipment and systems of machines that are not portable by hand while working, including groups of machines working together; its scope begins at the point where the supply connects to the machine’s electrical equipment. There is a 2016 edition and a 2021 amendment, and a consolidated version is published.
It is not a standard for “every panel”. For a control panel that belongs to a machine it is usually mentioned together with 61439; it may not directly concern a plant’s main distribution panel that has nothing to do with a machine. Confirm which applies in which scope from the contract and from the machine manufacturer’s conformity file.
IEC 60529 and IEC 62262
The IP code (IEC 60529) classifies the degrees of protection provided by enclosures; the IK code (IEC 62262) is a separate standard for protection against external mechanical impacts. Both only classify: which class is sufficient is decided by the environment, the specification and the relevant product or assembly standard. Examples such as “this IP indoors, that IP outdoors” in short summaries are not a standard’s rule; washing, dust, rain and condensation are assessed per project. For the balance between enclosure and ventilation, see section 7 of the existing guide.
IEC 60947 series
This is the series for low-voltage switchgear and controlgear devices: the devices that go inside the panel (protection, isolation, starting, control, terminals and so on) each fall under their own part. The first part contains general rules and applies when the relevant product standard requires it; its 2020 edition is published. A device complying with its own standard does not mean the panel is verified as an assembly; these are separate questions.
Short-circuit withstand and internal arc are separate subjects
Short-circuit withstand is a design verification subject tied to the assembly’s declared values (section 5 of the existing guide). Internal arc faults are covered in a separate document. IEC TR 61641:2014 was a guide for testing under arcing conditions due to an internal fault; its IEC webstore page states that it has been replaced by IEC TS 61641:2026. According to catalog entries, the new document covers internal arc fault protection of assemblies under the IEC 61439 series (passive protection through construction and active protection with arc management systems).
If a specification says “arc withstand”, have it state in writing which document, which edition and which class it refers to.
UL 508A and NFPA 79
UL 508A covers industrial control panels; NFPA 79 covers the electrical systems of industrial machinery. The first relates to panel construction and to certification programs such as UL’s panel shop program; the second is a rule used in machine building. On UL’s standards page the 3rd edition (2018) shows as active and was revised in 2025; confirm the edition in force for NFPA 79 per project. Neither replaces IEC 61439 or IEC 60204-1. For a panel going to North America, the national electrical codes (NEC in the US, CEC in Canada) and the project specification also come into play.
TEDAŞ specifications
TEDAŞ publishes its material technical specifications on the “Şartnameler” (specifications) page of its website. For low-voltage distribution panels, documents coded TEDAŞ-MLZ/2003-006.B, .C and .D (draft) are listed; medium-voltage switchgear has separate specifications. So “MV/LV distribution panels” is not a single specification, and when writing the code you must not drop the zero or the revision letter. The page does not say which of these three is in force; if your specification or contract cites a TEDAŞ code, confirm the current revision with TEDAŞ. A TEDAŞ specification comes into play when a contract or an authority refers to it, or when the panel is material belonging to the distribution network.
CE and TSE
They are not the same thing. The CE marking is the manufacturer’s statement that a product meets the relevant EU rules; TSE is the Turkish standards body. Which regulations apply to a panel and what “TSE conformity” can mean is in CE Marking and TSE for Panels: What Is the Difference?.
Which standard for which project?
The table is a starting point; the definitive list follows the specification and the contract.
| Project | Look first at | Note |
|---|---|---|
| In-plant automation and distribution panel | 61439-1, 61439-2 | Enclosure: 60529 |
| Control panel of a machine | 60204-1 | 61439: per contract |
| Main distribution and motor control panel | 61439-1, 61439-2 | Short-circuit value is an input |
| Distribution board for ordinary persons | 61439-3 | Check the scope limits |
| Construction site, EV charging, marina, PV, busbar trunking | 61439-4, -7, -8, -6 | Per part |
| Public distribution network material | 61439-5, TEDAŞ | Confirm code and revision |
| Panel with an internal arc requirement | IEC TS 61641 | Class comes from the spec |
| Panel going to North America | UL 508A, NFPA 79 | NEC and CEC apply too |
| Outdoor or washdown area | 60529, 62262 | Environment sets the class |
| EU and Türkiye market | LV, EMC, machinery legislation | See the CE note |
Common misreadings in short summaries
- “IEC 61439 is a single panel standard.” It is a multi-part series; the edition year differs from part to part.
- “Type test.” The 61439 term is design verification; “type test” comes from the old 60439 and from some institutional specifications.
- “The IP must be this.” The IP code classifies; the environment and the specification do the selecting.
- “60204-1 is for every panel.” It is for the electrical equipment of machines.
- “60947 is the panel standard.” It is the device series.
- “Short-circuit and arc are the same verification.” Internal arc is covered in a separate document.
- Writing the TEDAŞ code incompletely. Take the code and revision letter from the specification.
- “CE is a TSE document or a certificate.” CE is the manufacturer’s declaration; TSE is a standards and certification body.
- “UL 508A and NFPA 79 cover the same thing.” One is for panels, the other for the electrical system of machines.
Where to start
First put in writing which documents, in which editions, the specification and contract cite; then check whether the panel belongs to a machine, which environment it goes to and which market it ships to. Who will perform the design verification and the routine verification, and which short-circuit value will be the input, also need to be settled at the quote stage. If you have a specification, send it with your quote request; you can see the scope on our Control panel design and manufacturing page.
Sources
IEC webstore pages:
- IEC 61439-1:2020
- IEC 61439-2:2020
- IEC 61439-3:2024
- IEC 61439-4:2023
- IEC 61439-5:2023
- IEC 61439-6:2012
- IEC 61439-7:2022
- IEC 61439-8:2026
- IEC 60204-1:2016 and 2021 amendment (consolidated version)
- IEC 60529 (consolidated version)
- IEC 62262
- IEC 60947-1:2020
- IEC 60947 series parts list
- IEC TR 61641:2014 (page states it is replaced by TS 61641:2026)
Other: